![background image](http://html1.mh-extra.com/html/daikin/reyq96mtju/reyq96mtju_design-installation-and-testing-instruction_4175824035.webp)
Si39-406
Installation
General Information
29
Not
recommendable
but in case of
emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you
may follow the installation method mentioned below.
After the work is finished, make sure to check that is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening
torque suddenly increases. From that position, further tighten the flare nut the angle shown below:
Pipe size in. (mm)
Further tightening angle
Recommended arm length of tool
φ
1/4" (6.4)
60 to 90 degrees
Approx. 6" (150mm)
φ
3/8" (9.5)
60 to 90 degrees
Approx. 8" (200mm)
φ
1/2" (12.7)
30 to 60 degrees
Approx. 10" (250mm)
φ
5/8" (15.9)
30 to 60 degrees
Approx. 12" (300mm)
Summary of Contents for REYQ96MTJU
Page 1: ...Design Installation Testing Instruction R410A Heat Recovery 60Hz REYQ96MTJU Si39 406...
Page 6: ...Si39 406 iv Table of Contents...
Page 34: ...Installation Si39 406 28 General Information Flaring Procedure...
Page 68: ...Installation Si39 406 62 General Information Caution Caution label 3P124617 4P124614...
Page 114: ...Appendix Si39 406 108 General Information 3P135887 1...
Page 126: ...Appendix Si39 406 120 General Information 7 8 3 BS Unit BSVQ36MVJ BSVQ60MVJ 4D045338...
Page 128: ...Appendix Si39 406 122 General Information 7 9 2 Field Wiring REYQ96MTJU 3D042647A...
Page 156: ...Refrigerant Piping Si39 406 150 Installation Manual REYQ96MTJU...
Page 158: ...Refrigerant Piping Si39 406 152 Installation Manual REYQ96MTJU...
Page 230: ...Precautions for New Refrigerant R410A Si39 406 224 Precautions for New Refrigerant R410...
Page 236: ...375 Park Avenue Suite 3308 New York N Y 10152 info daikinac com www daikinac com...