Test Operation
SiBE811001EB
63
CONVENI-PACK
(1)
European/International Technical Standard setting the limits for voltage changes.
Voltage flucruations and flicker in public low-voltage supply systems for equipment with
rated current
≤
75A
(2)
European/International Technical Standard setting the limits for harmonic currents produced
by equipment connected to public low-voltage systems with input current > 16A and
≤
75A
per phase.
Operation output wiring connections
Connect operation output wiring to the X2M terminal block and clamp as indicated by the
following diagram:
X2M wire specifications
Remote operating switch wiring connections
When installing a remote operating switch, clamp as indicated by the following diagram:
X3M wire specifications
Caution
For Remote switch, use non-voltage contact for microcurrent (not more than 1mA, 12VDC)
If the remote operating switch will be used to start and stop the unit, set the operating switch
to “REMOTE”.
Electric wire thickness
0.75~1.25mm
2
Max. wiring length
130m
Electric wire thickness
0.75~1.25mm
2
Max. wiring length
130m
Clamp (1)
X3M
2
1
Secure remote
operating switch
wiring to the resin
block using a clamp
(field supply).