Troubleshooting
CONVENI-PACK
308
[Protection Device]
[Actuator]
[data]
[INV.]
[Error_code]
[capacity_control]
[Retty]
HPS actuation
S1PH
Actuation of the HPS (Actuation:1)
52ci
INV_52C compressor (ON/OFF: 0/1)
driving_[X26A]
Refrigeration solenoid valve signal ON/OFF (1/0)
Mulfunction_[X25A]
Abnormal signal ON/OFF (1/0)
INV_FAN_[X28A]
INV cooling fan ON/OFF (1/0)
Y1E
Y1E opening degree (0 to 480 Pls)
Y2E
Y2E opening degree (0 to 480 Pls)
Mtd
Target discharge pipe temperature
Ftc
Frequency table values (frequency is determined from these values.)
INV_rps
INV_rps (revolution speed) display
Lpm
Target evaporating temperature equivalent saturation pressure
total_Amp
Overall current
TgSH
Discharge SH
InvHz
Inverter frequency
Inv_1_Amp
Inverter primary current
Inv_2_Amp
Inverter secondary current
Error_code
Refer to
∗
1 on next page.
oil_collect_Hz_up
Capacity control: Signal that forces the increased frequency in oil collection conditions
F1
INV. discharge gas temperature retry count
F5
Low pressure protection retry count
F9
INV_E5 (lock) retry count
F10
INV_L9 (start-up failure/position inconsistency) retry count
F11
INV_L8 (overcurrent) retry count
F12
INV_L5 (instantaneous overcurrent) retry count
F13
INV_U2 (insufficient voltage) retry count
F14
INV_L4 (fin temperature increase) retry count
F17
INV_P1 (voltage equilibrium) retry count