SiBE811001EB
Troubleshooting
CONVENI-PACK
278
8.5.20 Refrigerant Shortage Alert
Error Code
U0
Applicable
Models
LCBKQ3AV1
Method of Error
Detection
Judged by aperture of electronic expansion valve and each temperature and pressure.
Error Decision
Conditions
When electronic expansion valve is fully open and the conditions below are met:
Supposed
Causes
Stop valve is not opened
Refrigerant shortage
Refrigerant clogging (piping error)
(Electronic expansion valve for injection, electronic expansion valve and filter in showcase)
Leakage of refrigerant
Improper torque of stop valve cover
Moisture choke
Troubleshooting
LED Indications
First digit
l h k l h h l
Second digit
l k h h h h h
OR
• Td >120°C
• Td >110°C continues for 15 sec.
• Td >105°C continues for 90 sec.
Check the clogging of
refrigerant system.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged.
Open the stop valve.
Stop valve is not
opened.
YES
NO
Remedy the cause.
Charge the appropriate amount
of refrigerant.
Does the
refrigerant leak?
YES
NO
Recover refrigerant. After
vacuum drying, refill an
appropriate amount of
refrigerant.
Is the refrigerant
amount appropriate?
NO