SiBE811001EB
Troubleshooting
CONVENI-PACK
152
3. Indoor Status Display
1/2
1. Unit No.
Select the Unit No. you want to check.
2. FAN
Tap, speed (rpm)
3. FLAP
Swing, fixed
4. Speed
Fan speed (rpm)
5. EV
Degree that electronic expansion valve is open
(pls)
6. MP
Drain pump ON/OFF
7. 52H
Electric heater ON/OFF
8. Hu
Humidifier ON/OFF
9. Anti-freezing
Anti-freezing control ON/OFF
3. Indoor Status Display
2/2
1. Unit No.
Select the Unit No. you want to check.
SkyAir
VRV
2. Th1
Suction air thermistor
Suction air thermistor
3. R2T
Heat exchanger
thermistor
Heat exchanger liquid
pipe thermistor
4. R3T
—
Heat exchanger gas
pipe thermistor
5. Th4
Discharge air
thermistor
Discharge air
thermistor
6. Th5
—
—
7. Th6
—
—
4. Outdoor Status
Display
1. Unit No.
Select the Unit No. you want to check.
2. FAN Tap 1
Fan tap
3. COMP
Compressor power supply frequency (Hz)
4. Y1E
Degree that electronic expansion valve is open
(pls)
5. SV1
Solenoid valve ON/OFF
SkyAir
VRV
6. Th1
Outdoor air thermistor
—
7. R2T
Heat exchanger
thermistor
—
8. R3T
Discharge pipe
thermistor
—
5. Forced Defrost
(SkyAir only)
1. Forced defrost ON
Enables the forced defrost operation.
2. Forced defrost OFF
Disables the forced defrost operation.
6. Error Display
Selection
1. Warning display ON
Displays a warning on the screen if an error
occurs.
2. Warning display OFF No warning is displayed.
3. Error display ON
Displays the error on the screen.
4. Error display OFF
Displays neither errors nor warnings.
7. Unit No. Transfer
1. Current Unit No.
A unit No. can be transferred to another.
2. Transfer Unit No.
8. Sensor Address
Display
{
Unit No.: 0 - 15
Select the Unit No. you want to check.
{
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
BS unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
{
Data
The corresponding data will be displayed, based
on the Unit No. and Code selected.
Service Menu
Item 2
Remarks