![background image](http://html1.mh-extra.com/html/daikin/lryeq16ay1/lryeq16ay1_service-manual_3234341156.webp)
Troubleshooting
SiBE811001EB
155
CONVENI-PACK
8.3
Setting with the BS Button
8.3.1 Outdoor Unit
Using the BS buttons on the outdoor unit main PCB (A1P) enable a various settings below:
The following 3 modes are available:
• Setting mode 1 ..... Initial state (while in normal operation). This mode indicates the current operation state (normal,
abnormal, preparing).
(H1P: OFF)
• Setting mode 2 ..... Used to modify the operation states and set program addresses. Usually used in servicing the
system.
(H1P: ON)
• Used to check the contents set in Setting mode 2.
(H1P: Blink)
Mode changing procedure
Using the MODE button, the modes can be changed follows.
BS1
MODE
BS2
SET
BS3
RETURN
BS4
BS5
RESET
TEST
Setting mode 1
Monitor mode
H1P
Press the BS1 (MODE button) once.
MODE
Blink
MODE
MODE
OFF
H1P
Setting mode 2
MODE
ON
H1P
Press and hold the BS1
(MODE button) for 5
seconds.
Press the BS1 (MODE
button) once.
Press the BS1 (MODE
button) once.
Simultaneously press and
hold the BS1 (MODE button)
and BS3 (RETURN button)
for a period of 5 seconds.
(Normal)
Setting mode 3
ON
H1P