SiBE811001EB
Troubleshooting
CONVENI-PACK
194
8.4.20 Low Pressure Sensor Abnormality
Error Code
E4
Applicable
Models
LRYEQ16AY1
Method of Error
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Error Decision
Conditions
Error is generated when the low pressure is dropped under compressor operation.
Operating pressure: -0.015MPa
Supposed
Causes
Abnormal drop of low pressure
Defective low pressure sensor
Defective outdoor unit PCB
Stop valve is not opened.
Refrigerant shortage
Moisture choke