Troubleshooting
SiBE811001EB
193
CONVENI-PACK
∗
1. Make a comparison between the voltage of the pressure sensor and that read by the pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector, and then convert it to pressure
according to information on P.295.)
∗
2: Make measurement of voltage of the pressure sensor.
Refer to P.285.
Replace the outdoor unit main
PCB (A1P) or sub PCB (A2P).
NO
Service Checker
Connect the service checker to compare the “high pressure” value and the
actual measurement value by pressure sensor (Refer to
∗
1) by using the
service checker.
Check if the “high
pressure” value and the
actual measurement
value by pressure sensor
are the same.
YES
· The high pressure sensor is normal, and the pressure detected with the
PCB is also normal.
· The high pressure has really become high.
CHECK 1
Referring to information on P.285, remove the causes by which
the high pressure has become high.
A
+5V Connector for high
pressure sensor
X32A (Red)
Micro-computer
A/D input
Make measurement of DC
voltage between these wires.
Red
Black
White
High
pressure
sensor
(4)
(3)
(2)
(1)
CHECK 1