Outline of Functions (Outdoor unit)
SiBE811001EB
105
CONVENI-PACK
(3) Oil recovery control
Oil recovery performed only when set in service mode 2-19 (Toil_BU).
(4) Fan control
After compressor operation, INV. cooling fan starts up. After the compressor stops, INV. cooling
fan also stops.
(5) Discharge pipe temperature control
(6) Subcooling control
SH control is performed based on the difference between the heat exchanger outlet (BU_Tg)
and inlet (BU_TL).
Y2E: Controlled at target BU_TgSH = 5°C.
During wet avoiding opening degree of Y2E is subtracted.
YES
OR
YES
OR
YES
• BU_LP > 0.0588MPa
• Continuous operation
time for operation mode 1
(that for Toil_BU) or more
R2 signal stays on.
NO
NO
NO
R2 signal: OFF
• BU_LP > 0.0588MPa
• 30 sec. have passed
R2 signal: ON
• BU_LP > 0.0784MPa
• BU_LP < 0MPa
• 60 sec. have passed
Oil recovery terminated
&
&
• BU_Td > 100˚C
• BU_Td rises quickly
• BU_Td < 50˚C
• Y1E_pls
≤
43pls
&
OR
Discharge pipe
temperature
control
Droop control via Td rise
Y1E control by Td
When the conditions on the right are met.
• Compressor operation is stepped down
• Opening degree of Y1E is added
OR
• BU_Td > 105˚C continues for 45 consecutive sec. or more
• BU_Td: Temperature detected by discharge pipe temperature thermistor of
booster unit
• BU_Tg: Temperature detected by heat exchanger outlet thermistor of
booster unit
• BU_TL: Temperature detected by heat exchanger inlet thermistor of
booster unit
• BU_TgSH: BU_Tg–BU_TL (SH control)
• BU_Tf
∗
Booster INV. fin temperature
When the below condition is released.
Wet avoiding
control
BU_Td optimal
control
• Close Y1E
Y1E
Controls at target Td = 85˚C
• BU_Td drops for 20 consecutive seconds.