Control Specification
SiENBE12-713
82
Function and Control
3. Control Specification
3.1
Mode Hierarchy
Outline
There are two modes; the mode selected in user’s place (normal air conditioning mode) and
forced operation mode for installation and providing service.
Detail
1. For heat pump model
There are following modes; stop, cooling (includes drying), heating (include defrosting)
2. For cooling only model
There are following models; stop and cooling (including drying).
Note:
Unless specified otherwise, an indoor dry operation command must be regarded as cooling
operation. An indoor fan operation command cannot be made in a multiple indoor unit. (A forced
fan command to the indoor unit from the outdoor unit must be made during forced operation.)
Determine Operating Mode
Judge the operating mode command set by each room in accordance with the instructing
procedure, and determine the operating mode of the system.
The following procedure will be taken as the modes conflict with each other.
*1.The system will follow the mode determined first. (First-push, first-set)
*2.For the rooms set with different mode, select stand-by mode. (Operation lamp flashes)
Air conditioner control mode
Forced operating mode
Forced cooling
Forced heating
Check incorrect wiring
Normal operating mode
Cooling
Heating
Defrosting
Stop mode (except for cooling/heating modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop
(R1373)
Air conditioner control mode
Forced operating mode
Forced cooling
Check incorrect wiring
Normal operating mode
Cooling
Stop mode (except for cooling modes by indoor command)
Preheat operation
During C (capacitor) is discharging
Stop
(R1374)
Summary of Contents for FTKS20D3VMW
Page 11: ...Introduction SiENBE12 713 x...
Page 47: ...Specifications SiENBE12 713 36 Specifications...
Page 113: ...Control Specification SiENBE12 713 102 Function and Control...
Page 235: ...Instruction SiENBE12 713 224 System Configuration...
Page 297: ...Check SiENBE12 713 286 Service Diagnosis...