SiENBE12-713
Instruction
System Configuration
215
Do not install the air conditioner at any place where
flammable gas may leak out.
If the gas leaks out and stays around the air conditioner, a
fire may break out.
Be sure to install an earth leakage breaker.
Unless it is installed, an electric shock may result.
Be sure the air conditioner is electrically grounded.
Do not connect the grounding conductor to a gas pipe,
water pipe, lightning arrester and the grounding conductor
for a telephone.
Imperfect grounding work may result in an electric shock.
Execute complete drain piping for perfect drainage.
Incomplete piping may result in a water leakage.
The appliance is not intended for use by young
children or infirm persons without supervision. Young
children should be supervised to ensure that they do
not play with the appliance.
If the temperature or the humidity is beyond the following
conditions, safety devices may work and the air
conditioner may not operate, or sometimes, water may
drop from the indoor unit.
COOLING
HEATING
DB: Dry bulb temperature (°C)
WB: Wet bulb temperature (°C)
The setting temperature range of the remote control is 16°C to
32°C.
Regarding places for installation
•
Is the air conditioner installed at a well-ventilated
place where there are no obstacles around?
•
Do not use the air conditioner in the following places.
a. Filled with much mineral oil such as cutting oil.
b. Where there is much salt such as a beach area.
c. Where sulfured gas exists such as a hot-spring resort.
d. Where there are considerable voltage fluctuations such
as a factory or plant.
e. Vehicles and vessels.
f. Where there is much spray of oil and vapor such as a
cookery, etc.
g. Where there are machines generating electromagnetic
waves.
h. Filled with acid and/or alkaline steam or vapor
•
Is a snow protection measure taken?
For details, consult your dealer.
3. Operation range
OUTDOOR UNIT
INDOOR
OUTDOOR
TEMPERA-
TURE
TEMPERATURE
HUMIDITY
R35
%
45
%
60
DB
18 to 33 80% or
below
DB
-15 to 46
WB
18 to 24
RY35
%
45
%
60
DB
18 to 33 80% or
below
DB
-5 to 46
WB
12 to 24
R71
%
100
%
125
RP71
%
100
%
125
REP71
%
100
%
125
DB
21 to 35
80% or
below
DB
-15 to 46
WB
14 to 25
RY71
%
100
%
125
RYP71
%
100
%
125
RYEP71
%
100
%
125
DB
18 to 35
80% or
below
DB
-5 to 46
WB
12 to 25
RZP71
%
100
%
125
DB
21 to 35 80% or
below
DB
-5 to 50
WB
14 to 25
RQ71
%
100
%
125
DB
18 to 37 80% or
below
DB
-5 to 46
WB
12 to 28
RR71
%
100
%
125
DB
18 to 37 80% or
below
DB
-15 to 50
WB
12 to 28
RZQ71
%
100
%
125
%
125
DB
18 to 37 80% or
below
DB
-15 to 46
WB
12 to 28
RS50
%
60
RKS35
%
50
%
60
RXS35
%
50
%
60
DB
21 to 32
80% or
below
DB
-10 to 46
WB
14 to 23
3MKS50
4MKS58
%
75
%
90
3MXS52
%
2MXS52
4MXS68
%
80
DB
21 to 32
80% or
below
DB
-10 to 46
WB
14 to 23
RMKS112
%
140
%
160
RMKS112
%
140
%
160
DB
21 to 32 80% or
below
DB
-5 to 46
WB
14 to 23
OUTDOOR UNIT
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
RY35
%
45
%
60
DB
15 to 27
DB
-9 to 21
WB
-10 to 15.5
RY71
%
100
%
125
RYP71
%
100
%
125
RYEP71
%
100
%
125
DB
15 to 27
DB
-9 to 21
WB
-10 to 15.5
RZP71
%
100
%
125
DB
15 to 27
DB
-14 to 21
WB
-15 to 15.5
RQ71
%
100
%
125
DB
10 to 27
DB
-9 to 21
WB
-10 to 15
RZQ71
%
100
%
125
%
140
DB
10 to 27
DB
-19.5 to 21
WB
-20 to 15.5
RXS35
%
50
%
60
DB
10 to 30
DB
-14 to 24
WB
-15 to 18
3MXS52
%
2MXS52
%
4MXS68
%
80
DB
10 to 30
DB
-14 to 21
WB
-15 to 15.5
RMXS112
%
140
%
160
DB
10 to 30
DB
-14 to 21
WB
-15 to 15.5
4. INSTALLATION SITE
Summary of Contents for FTKS20D3VMW
Page 11: ...Introduction SiENBE12 713 x...
Page 47: ...Specifications SiENBE12 713 36 Specifications...
Page 113: ...Control Specification SiENBE12 713 102 Function and Control...
Page 235: ...Instruction SiENBE12 713 224 System Configuration...
Page 297: ...Check SiENBE12 713 286 Service Diagnosis...
Page 316: ...SiENBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points...