Specifications
25
50Hz 230V
Model
CTXG50EV1BW
CTXG50EV1BS
Cooling
Heating
Cooling
Heating
Rated Capacity
5.0kW Class
5.0kW Class
Front Panel Color
Mat Crystal White
Mat Crystal Silver
Air Flow Rates
m³/min
(cfm)
H
11.3 (398)
12.6 (444)
11.3 (398)
12.6 (444)
M
9.1 (320)
10.6 (373)
9.1 (320)
10.6 (373)
L
7.1 (250)
8.7 (306)
7.1 (250)
8.7 (306)
SL
6.7 (236)
7.7 (271)
6.7 (236)
7.7 (271)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
40
Speed
Steps
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Air Direction Control
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.15-0.14-0.13
0.15-0.14-0.13
0.15-0.14-0.13
0.15-0.14-0.13
Power Consumption (Rated)
W
30
30
30
30
Power Factor
%
90.9-93.2-96.2
90.9-93.2-96.2
90.9-93.2-96.2
90.9-93.2-96.2
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
275×840×150
275×840×150
Packaged Dimensions (H×W×D)
mm
222×894×345
222×894×345
Weight
kg
9
9
Gross Weight
kg
13
13
Operation
Sound
H/M/L/SL
dBA
47/41/35/32
47/41/35/32
47/41/35/32
47/41/35/32
Sound Power
H
dBA
64
64
64
64
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
12.7
Drain
mm
φ
18.0
φ
18.0
Drawing No.
3D051105
3D051106
Model
FTXS20D3VMW
FTXS20D3VML
Cooling
Heating
Cooling
Heating
Rated Capacity
2.0kW Class
2.0kW Class
Front Panel Color
White
Silver Line
Air Flow Rates
m³/min
(cfm)
H
8.7 (307)
9.4 (332)
8.7 (307)
9.4 (332)
M
6.7 (237)
7.6 (268)
6.7 (237)
7.6 (268)
L
4.7 (166)
5.8 (205)
4.7 (166)
5.8 (205)
SL
3.9 (138)
5.0 (177)
3.9 (138)
5.0 (177)
Fan
Type
Cross Flow Fan
Cross Flow Fan
Motor Output
W
40
40
Speed
Steps
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Air Direction Control
Right, Left, Horizontal, Downward
Right, Left, Horizontal, Downward
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.16
0.16
0.16
0.16
Power Consumption (Rated)
W
35
35
35
35
Power Factor
%
95.1
95.1
95.1
95.1
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
283×800×195
283×800×195
Packaged Dimensions (H×W×D)
mm
265×855×340
265×855×340
Weight
kg
9
9
Gross Weight
kg
12
12
Operation
Sound
H/L/SL
dBA
38/25/22
38/28/25
38/25/22
38/28/25
Sound Power
H
dBA
56
56
56
56
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
9.5
Drain
mm
φ
18.0
φ
18.0
Drawing No.
3D051085
3D051086
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Summary of Contents for FTKS20D3VMW
Page 11: ...Introduction SiENBE12 713 x...
Page 47: ...Specifications SiENBE12 713 36 Specifications...
Page 113: ...Control Specification SiENBE12 713 102 Function and Control...
Page 235: ...Instruction SiENBE12 713 224 System Configuration...
Page 297: ...Check SiENBE12 713 286 Service Diagnosis...
Page 316: ...SiENBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points...