SiENBE12-713
Outdoor Unit
Removal Procedure
295
8
Disconnect the
connector for overload
protector [S40].
9
Remove the OL wire
harness and the
compressor wire
harness together from
the partition plate.
10
Use long-nose pliers or
the like to pull out the
clamp.
"
Detach the clamp.
"
Just pull the push-mount
type out of position.
11
Disconnect the
connector for relay
harness of compressor.
Step
Procedure
Points
Cl
a
mp
(R642
3
)
Cl
a
mp