SiAU18-715
Troubleshooting for SkyAir Indoor Unit
Troubleshooting
347
5.14
Malfunction of Field Setting Switch
Remote
Controller
Display
UA
Applicable
Models
FFQ, FCQ, FBQ, FHQ
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Incorrect field setting
Supposed
Causes
Indoor-Outdoor (BP) transmission line
Faulty remote controller wiring
Troubleshooting
Does the system conduct
normal operation?
NO
Do the
microcomputer
normal monitors HAP on all
indoor unit PCB
blink?
NO
NO
Is the field
setting for pair / twin
system correct?
YES
YES
YES
YES
NO
YES
Turn the power supply off once,
and back on to restart.
NO
Are the wirings
between indoor and BP
unit correctly
connected?
Are the wirings
between indoor and BP
unit correctly
connected?
NO
YES
Is 220 ~ 240
VAC between No.1 and
3 of X2M terminal
(indoor unit)?
YES
Is the
remote controller
connected to one or more
indoor units?
NO
YES
Is the
remote controller
wiring jumped between
indoor units?
NO
(Q0544)
Connect the remote controller
correctly.
Remove the jumper.
Set correctly.
Connect correctly.
Check the power supply system
inside the indoor unit.
Could be incorrect wiring.
Check again.
Connect correctly.
Replace the indoor unit PCB.
Normal
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...