SiAU18-715
Troubleshooting for Outdoor Unit
Troubleshooting
369
7.10
Malfunction of Discharge Pipe Thermistor (R2T)
Remote
Controller
Display
J3
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by discharge pipe temperature
thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Supposed
Causes
Defect of thermistor (R2T) for outdoor unit discharge pipe
Defect of outdoor unit PCB (A1P)
Troubleshooting
∗
Refer to thermistor resistance / temperature characteristics table on P405.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector is
connected to outdoor unit
PC board (A1P).
Resistance
is normal when
measured after
disconnecting the thermistor
R2T from the outdoor
unit PC board.
(5.0k
Ω
~
640k
Ω
)
Replace outdoor unit PC
board (A1P).
(Q0559)
Connect the thermistor
and turn on again.
NO
Replace the thermistor
(R2T).
NO
YES
YES
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...