SiAU18-715
Troubleshooting for Outdoor Unit
Troubleshooting
399
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
an indoor unit
once connected been
remove or its address
changed?
Is
the master
controller's connector for
setting master controller
disconnected?
Is the power
supply turned on for
indoor units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is
transmission with
all indoor units
malfunctioning?
Is the
group No. of
malfunctioning indoor
units set?
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Connect the connector
correctly.
NO
Reset power supply
simultaneously for all
optional controllers for
centralized control.
YES
NO
Turn indoor unit's power
supply.
NO
YES
Fix the wiring correctly.
NO
YES
NO
YES
Fix the wiring correctly.
NO
YES
Replace the central PC
board.
YES
(Q0584)
Set the group No.
correctly.
NO
Replace indoor unit PC
board.
YES
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...