Indoor Unit (SkyAir Models)
SiAU18-715
124
Function
Mode Conflict
[Overview]
While the indoor unit for another room and the outdoor unit are operating, when the indoor unit
for the own room is activated, the operation mode which can be selected in the own room has
some restrictions as mentioned below.
i)
In case an priority for operation mode selection is given to the own room by setting the dip
switch of outdoor unit;
→
The own room can be operated in any mode.
ii)
In case an priority for operation mode selection is not given to the own room by setting the
dip switch of outdoor unit;
→
The unit can be operated as follows:
{
:Operational
∗:
The unit for another room is switched into non-operational condition.
× : Non-operational
* Operation of the indoor unit for the own room during non-operation.
•
Fan = OFF
•
Louver = becomes horizontal position.
•
ON LED on the remote controller = blinks.
•
Indication of "under central control" on the remote controller = displayed.
Note:
During automatic operation, at the time of changing operation mode to Automatic cooling
or Automatic heating, the unit is operated as the table shown above.
Outdoor unit
operation mode
when an operation
mode for the own
room is selected.
(The outdoor unit
is operated in the
mode as
mentioned below.)
Operation mode selected in the own room
Cooling or
Automatic cooling
(Note)
Dry
Blowing
Heating or
Automatic heating
(Note)
Cooling
{
{
{
×
Heating
×
×
×
{
Blowing
{
{
{
{
∗
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...