Protection Control
SiAU18-715
94
Function
4.6
Dew Condensation Prevention
Control
Outline
According to the dew condensation prevention status sent from the BP unit. The compressor
output frequency is regulated to decrease the compressor capacity in order to prevent the
indoor unit from dew condensation.
Detail
Zones are produced based on the dew condensation prevention status signal sent from the BP
unit (Indoor unit), and the dew condensation prevention control prevents dew condensation of
the indoor unit.
Recovery zone: Lift the control
Increase zone: 1 step up/60sec.
Keep zone: Frequency is not controlled
Decrease zone: 1 step down/60sec. SVG open at 52Hz
The temperature in above figure depends on models and actual room temperature. (Reference
value)
˚C
14.5
13
12.5
12
Recovery zone
Increase zone
Keep zone
Decrease zone
Indoor unit heat exchanger
temperature
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...