Field Setting
SiAU18-715
134
Test Operation
3. Field Setting
3.1
Field Setting from Outdoor Unit
3.1.1
Setting by Dip Switches
The following field settings are made by dip switches on PC board.
Dipswitch
Setting item
Description
No.
Setting
DS1-1
ON
Cool / Heat
change over
setting
Used to set cool / heat change over setting by remote
controller equipped with outdoor unit. (Note 1)
OFF (Factory set)
DS1-2
ON
Not used
Do not change the factory settings.
OFF (Factory set)
Connect the cool/heat selector (optional accessory) to the terminals (A, B and C) on the outdoor PC
board (A4P).
Set the cool/heat selector switch DS1-1 from “IN (inside) ” (which is selected at the factory
before shipment) to “OUT (outside) ”.
A B C
A B C
A4P
A2P
Cool/heat
selector
DS1-1
switch knob
OUT
IN
ON/OFF
DS1 1 2
C/H
SELECTOR
Cool/heat selector connection procedure
Set the remote controller only when changing over the operation mode between cooling and heating
using the remote controller installed in the outdoor.
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...