SiAU18-715
Troubleshooting for Outdoor Unit
Troubleshooting
381
7.22
Malfunction of Transmission between Inverter and
Control PCB
Remote
Controller
Display
LC
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
Malfunction of connection between the inverter microcomputer and outdoor control
microcomputer
Defect of outdoor unit PCB
Defect of noise filter
External factor (Noise etc.)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
microcomputer
monitor (green) on the
outdoor unit PC board
(A1P) is blinking.
Check the noise filter
(A3P) for disconnection,
and check the power
supply wiring.
(Q0571)
Replace outdoor unit PC
board (A1P).
YES
The
voltage
between red and
white of X1A on the
inverter unit is the
power supply
voltage.
Replace outdoor unit PC
board (A1P).
↓
When the LC malfunction
occur again, replace
control PC board.
YES
NO
NO
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...