Caution for Diagnosis
SiAU18-715
304
Troubleshooting
1.4
Troubleshooting with
the LED on the BP Unit
LEDA(H1P)
LED1(H2P)
LED2(H3P)
LED3(H4P)
LED4(H5P)
(Q0395)
HIGH PRESSURE PROTECTOR WORKED, OR FREEZE-UP IN OPERATING UNIT OR STAND-BY UNIT
POWER SUPPLY FAULT OR [NOTE 2]
DIAGNOSIS
DIAGNOSIS
LED-2 LED-3
LED-1
GREEN
THERMISTOR ABNORMALITY
RED
[NOTE 1]
NORMAL
→
CHECK INDOOR OR OUTDOOR UNIT
RED
GREEN
FLASH
INTERCOMMNICATION TO
OUTDOOR UNIT : NORMAL
ELECTRONIC EXPANSION VALVE ABNORMALITY
LED-4
NORMALLY FLASHING
OFF
NORMAL
ABNORMALITY
→
CHECK INTER-UNIT WIRING
ON
MALFUNTION DETECTION
IRRELEVANT
NORMALLY OFF
LED-B (GREEN)
MICROCOMPUTER
: NORMAL
LED-A
ABNORMALITY
→
CHECK INTER-UNIT WIRING
NOTES 1.TURN THE POWER OFF THEN ON AGAIN, IF THE LED DISPLAY RECURS, THE BRANCH PROVIDER UNIT PCB IS
FAULTY.
2.TURN THE POWER OFF AND THEN ON AGAIN, IF THE LED DISPLAY RECURS, TURN THE POWER OFF AND
DISCONNECT LINE 2 OF INTER-UNIT WIRING FOR ALL UNITS, THEN TURN THE POWER ON AGAIN.
<IF LED-A IS OFF : >
THE BRANCH PROVIDER UNIT PCB IS FAULTY.
<IF LED-A IS FLASHING : >
THE INDOOR UNIT PCB IS FAULTY. TURN THE RECONNECT LINE 2 OF ALL INTER-UNIT WIRING AND CHECK
THE DAIGNOSIS BY LEDS ON INDOOR UNIT PCB.
3P058760C
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...