Indoor Unit (SkyAir Models)
SiAU18-715
122
Function
Program Dry
Operation
Function
The points of thermostat ON or OFF are determined according to the suction air temperature at
the startup of unit operation.
The set temperature and flow rate are not displayed on remote controller.
1. Thermostat ON point (T
ON
) according to suction air temp. (T
S
).
2. Operation condition
Auto-restart
Function
If there is a power cut when the unit is operating, it will automatically resume the same operating
mode when the power is restored.
Caution
When performing maintenance and the power supply is to be shut off, be sure to turn the remote
controller’s ON/OFF switch OFF first.
Shutting the power supply switch off while the ON/OFF switch is still ON is dangerous because
the “power failure automatic reset function” will cause the indoor fan to start turning
immediately, or the outdoor unit fan to automatically start turning three minutes after the power
supply is turned back on.
Suction air temp
T
ON
(°C)
Td
ON
(°C)
Ts
>
24°C
24°C
≥
Ts
>
16°C
16°C
≥
Ts
Ts
Ts
16°C
1.5
1.0
1.0
Compressor condition
ON
OFF
Setting of flow rate
Angle of flap
Air flow direction set with remote
controller
L operation
Set angle
Set angle
OFF
Set angle
Set angle
Operation startup
(Differential)
(S1120)
Thermostat
ON
Thermostat
OFF
Suction air temp
. Ts
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...