SiAU18-715
Basic Control
Function
79
∆
D Control
Receiving the capacity request signal from the indoor unit, the outdoor unit corrects its target
pressure for capacity control.
Controls
∆
D signal from indoor unit as follows.
UP control :
When the UP command come from more than one indoor unit among
thermostat-ON indoor units.
Down control : When the down command come from all indoor units among thermostat-ON
indoor units.
Keep control : Except for the above
About detail of
∆
D signal, refer to P96
Cooling Operation
TeS = TeS initial value + KTe2
KTe2 : Correction value by
∆
D signal in cooling.
KTe2 = 0
(without correction)
∆
D control
Keep the current KTe2
KTe2 = KTe2 0.5
KTe2 = KTe2 + 0.5
Up control by
∆
D signal
continues 120 sec.
Down control by
∆
D signal
continues 120 sec.
During compressor frequency PI
control (KTe2 = 0)
Not during compressor frequency PI
control
(Q0396)
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...