SiAU18-715
Indoor Unit (SkyAir Models)
Function
119
2. Heating
2-1 Basic operation
2-1-1 When compressor stops during drain pump ON after compressor operation started
3
min
2-1-2 When compressor stops during drain pump OFF after compressor operation started
3
min
2-2
Operations when an occurrence of drain water level abnormality
2-2-a) Behavior between occurrence and recovery of drain water level abnormality
Drain pump
ON
OFF
ON
OFF
Compressor
ON
OFF
5min
20 min
5min
Compressor
ON
OFF
20 min
20 min
Drain pump
In heating operation of the unit equipped with a humidifier, when "Interlocking of drain pump /
humidifier" (15(25)-3) is set to "yes" (02), the drain pump operates 20-min OFF and 3-min ON
repeatedly during compressor is in operation.
After compressor stops, residual operation will be conducted for 5 minutes.
2-2-a)-1 When a water level abnormality occurs during drain pump ON
Occurrence of drain water level abnormality
5
sec
A
10
sec sec
Compressor
ON
OFF
Error processing
5min
Abnormal
Normal
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
5min
Intermittent operation (*1)
After compressor stops due to water level abnormality, drain pump is operated intermittenly, i.e. 5 min
ON, 5 sec OFF and 5 min ON. (*1) The intermittent operation is executed regardless of recovery of abn.
Water level during the intermittent operation. (*2) When the abn. water level can not be recovered, the
latter 5 min ON operation is continued until recovery of the abnormality. (*3) On above diagram, the
system operation in the event of a water level abnormality occurrence differs between the drain pump ON
and OFF. The details are as follows.
1 The same operation as 1-2-a) "Behavior between occurrence and recovery of drain water level
abnormality" in the mode of cooling or dry.
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Note : ((2-2-a)-1 When a water level abnormality occurs during drain pump ON)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.
Summary of Contents for E Series
Page 1: ...SiAU18 715 Applied Models Super Multi Plus Cooling Only Super Multi Plus Heat Pump E Series ...
Page 87: ...Refrigerant Flow for Each Operation Mode SiAU18 715 74 Refrigerant Circuit ...
Page 139: ...Indoor Unit SkyAir Models SiAU18 715 126 Function ...
Page 177: ...Test Operation and Field Setting for RA Indoor Unit SiAU18 715 164 Test Operation ...
Page 299: ...Instruction SiAU18 715 286 Operation Manual 2 6 Ceiling Suspended Type ...
Page 326: ...SiAU18 715 Service Check Function Troubleshooting 313 ...
Page 423: ...Method of Replacing The Inverter s Power Transistors Modules SiAU18 715 410 Troubleshooting ...
Page 443: ...Wiring Diagrams SiAU18 715 430 Appendix ...
Page 449: ...SiAU18 715 vi Index ...