Troubleshooting for SkyAir Indoor Unit
SiENBE18-621
286
Troubleshooting
5.5
Malfunction of Indoor Unit Fan Motor
Remote Control
Display
A6
Applicable
Models
FFQ-B
Method of
Malfunction
Detection
Detection of abnormal fan speed by signal from the fan motor
Malfunction
Decision
Conditions
When fan speed does not increase
Supposed
Causes
"
Disconnection, short circuit or disengagement of connector in fan motor harness
"
Faulty fan motor (disconnection, poor insulation)
"
Abnormal signal from fan motor (faulty circuit)
"
Faulty PCB
"
Instantaneous fluctuation of power supply voltage
"
Fan motor lock
(Caused by motor or other external factors)
"
Fan does not turn due to a tangle of foreign matters.