Troubleshooting for RA Indoor Unit
SiENBE18-621
276
Troubleshooting
4.4
Thermistor or Related Abnormality (Indoor Unit)
Remote Control
Display
C4, C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation
∗
.
∗
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note:
The values vary slightly in some models.
Supposed
Causes
"
Faulty connector connection
"
Faulty thermistor
"
Faulty PCB
Troubleshooting
Check No.06
Refer to P.279
C4
: Heat exchanger temperature thermistor
C9
: Room temperature thermistor
Check the connector connection.
YE
S
Correct the connection.
Repl
a
ce the thermi
s
tor.
(Repl
a
ce the indoor
u
nit PCB.)
Repl
a
ce the indoor
u
nit PCB.
I
s
it norm
a
l?
I
s
it norm
a
l?
(R4696)
NO
Check No. 06
Thermi
s
tor re
s
i
s
t
a
nce check
YE
S
NO
Caution
Be
su
re to t
u
rn off power
s
witch
b
efore connect or di
s
connect connector,
or p
a
rt
s
d
a
m
a
ge m
a
y
b
e occ
u
rred.
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...