Indoor Unit (SkyAir Models)
SiENBE18-621
108
Function
Mode Conflict
[Overview]
While the indoor unit for another room and the outdoor unit are operating, when the indoor unit
for the own room is activated, the operation mode which can be selected in the own room has
some restrictions as mentioned below.
i)
In case an priority for operation mode selection is given to the own room by setting the dip
switch of outdoor unit;
→
The own room can be operated in any mode.
ii)
In case an priority for operation mode selection is not given to the own room by setting the
dip switch of outdoor unit;
→
The unit can be operated as follows:
#
:Operational
∗:
The unit for another room is switched into non-operational condition.
× : Non-operational
* Operation of the indoor unit for the own room during non-operation.
•
Fan = OFF
•
Louver = becomes horizontal position.
•
ON LED on the remote control = blinks.
•
Indication of "under central control" on the remote control = displayed.
Note:
During automatic operation, at the time of changing operation mode to Automatic cooling
or Automatic heating, the unit is operated as the table shown above.
Outdoor unit
operation mode
when an operation
mode for the own
room is selected.
(The outdoor unit
is operated in the
mode as
mentioned below.)
Operation mode selected in the own room
Cooling or
Automatic cooling
(Note)
Dry
Blowing
Heating or
Automatic heating
(Note)
Cooling
#
#
#
×
Heating
×
×
×
#
Blowing
#
#
#
#
∗
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...