SiENBE18-621
Field Setting
Test Operation
131
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
%
In setting mode 2, push the BS1 (MODE button) one time.
→
Setting mode 1 is entered and
H1P off.
During the setting mode 1 is displayed, “In low noise operation” and “In demand control” are
displayed.
2. Setting mode 2 (H1P on)
%
In setting 1, push and hold the BS1 (MODE button) for more than 5 seconds.
→
Setting
mode 2 is entered and H1P lights.
&
Push the BS2 (SET button) several times and match the LED display with the Setting No.
you want.
'
Push the BS3 (RETURN button) one time, and the present setting content is displayed.
→
Push the BS2 (SET button) several times and match the LED display with the setting
content (as shown on next page) you want.
(
Push the BS3 (RETURN button) two times.
→
Returns to
%
.
*
Push the BS1 (MODE button) one time.
→
Returns to the setting mode 1 and turns H1P off.
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...