Field Setting for SkyAir Indoor Unit
SiENBE18-621
140
Test Operation
4.5
Detailed Explanation of Setting Modes
4.5.1 Air Flow Direction Setting (FFQ)
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
4.5.2 Filter Sign Setting (FFQ & FHQ)
If switching the filter sign ON time, set as given in the table below.
Set Time
4.5.3 Range of Air Flow Direction Setting (FFQ)
Make the following air flow direction setting according to the respective purpose.
4.5.4 Fan Speed OFF When Thermostat is OFF (FFQ & FHQ)
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting
to “Fan OFF.”
∗
Used as a countermeasure against odor for barber shops and restaurants.
Setting Table
Mode No.
First Code No.
Second Code
No.
Setting
13 (23)
1
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Filter Specs.
Setting
Long Life
Contamination Light
01
2,500
Contamination Heavy
02
1,250
Mode No.
First Code No.
Second Code No.
Setting
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling
prevention)
Mode No.
First Code No.
Second Code No.
Setting
11(21)
2
01
—
02
Fan OFF
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...