SiENBE18-621
Field Setting for SkyAir Indoor Unit
Test Operation
141
4.5.5 Fan Speed Changeover When Thermostat is OFF (FFQ & FHQ)
By setting to “Set Fan Speed,” you can switch the fan speed to the set fan speed when the
heating thermostat is OFF.
∗
Since there is concern about draft if using “fan speed up when thermostat is OFF,” you should
take the setup location into consideration.
Setting Table
4.5.6 Wireless Setting (Address and MAIN/SUB Setting)
Explanation
If several infrared remote control units are used together in the same room (including the case
where both group control and individual remote control control are used together), be sure to set
the addresses for the receiver and infrared remote control. (For group control, see the attached
installation manual for the indoor unit.) If using together with a wired remote control, you have to
change the main/sub setting or the receiver.
Receiver Setting
Set the wireless address switch (SS2) on the transmitter board according to the table below.
When using both a wired and a infrared remote control for 1 indoor unit, the wired controller
should be set to MAIN. Therefore, set the MAIN/SUB switch (SS1) of the transmitter board to
SUB.
After completing setting, seal off the opening of the address switch and the MAIN/SUB switch
with the attached sealing pad.
Mode No.
First Code No.
Second Code No.
Setting
12(22)
3
01
LL Fan Speed
02
Set Fan Speed
Unit No.
No.1
No.2
No.3
Wireless Address
Switch (SS2)
MAIN
SUB
MAIN/SUB Switch
(SS1)
123 MS
SS2 SS1
(S1940)
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...