Field Setting for SkyAir Indoor Unit
SiENBE18-621
144
Test Operation
4.6
Centralized Group No. Setting
"
If carrying out centralized control with a central remote control and unified ON/OFF
controller, you have to set the group No. for each group by remote control.
"
To set the group No., first turn on the power supply of the central remote control, unified ON/
OFF controller and indoor unit.
Centralized
Group No. Setting
by Remote
Control
1. If the inspection/test button is pushed for 4 seconds or more when in the normal mode,
operation enters the “field set mode.”
2. Using the temperature control buttons, set the mode No. to “00.”
3. Push the inspection/test button to inspect the group No. display.
4. Using the programming time button, set the group No. for each group. (Group No. rises in
the order of 1-00, 1-01, ...1-15, 2-00 ...4-15, etc. The unified ON/OFF controller however
displays only the range of group numbers selected by the switch for setting each address.)
5. Push the timer ON/OFF button and enter the selected group No.
6. Push the inspection/test button and return to the normal mode.
∗
If the address has to be set individually for each unit for power consumption counting, etc., set
the mode No. to “30.”
Group No. Setting
Example
Note:
1. “F1,F2” indicates interface adapter for SkyAir series.
2. If not using remote controls, temporarily connect a remote control to set the group No., set
the group No. for centralized control, and then disconnect the controller.
Gro
u
p No.
Mode No.
Field
s
et
mode
Centr
a
l remote control
Unified ON/OFF controller
Indoor
u
nit
Gro
u
p No. for
centr
a
lized
control
No remote control
Remote control centr
a
lized control
(
au
tom
a
tic
a
ddre
ss
)
Summary of Contents for BPMKS967B2B
Page 1: ...SiENBE18 621 E Series Service Manual Applied Models Super Multi Plus Heat Pump...
Page 12: ...SiENBE18 621 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 19: ...List of Functions SiENBE18 621 8 List of Functions...
Page 33: ...Specifications SiENBE18 621 22 Specifications...
Page 69: ...Refrigerant Flow for Each Operation Mode SiENBE18 621 58 Refrigerant Circuit...
Page 121: ...Indoor Unit SkyAir Models SiENBE18 621 110 Function...
Page 169: ...Instruction SiENBE18 621 158 System Configuration FTXS 20 25 35C Indoor Unit...
Page 371: ...Method of Replacing The Inverter s Power Transistors Modules SiENBE18 621 360 Troubleshooting...
Page 393: ...SiENBE18 621 vi Index...