ENGLISH
40
A.D. M/M 1.1 A.D. M/T 1.0
A.D. M/T 2.2
A.D. T/T 3.0
A.D T/T 5.5
Work position:
Any position Any position
Any position
Facing upward
Facing upward
Max fluid temperature:
50°C
50°C 50°C 50°C 50°C
Max working temperature:
60°C
60°C 60°C 60°C 60°C
Max. pressure:
16 bar
16 bar
16 bar
16 bar
16 bar
Regulating range:
from 1 to 6 bar
from 1 to 9 bar from 1 to 15 bar from 1 to 15 bar from 1 to 15 bar
Maximum dimensions (LxHxD):
22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm
Fluid input hydraulic coupling:
1 ¼” male
1 ¼” male
1 ¼” male
1 ¼” male
1 ¼” male
Fluid output hydraulic coupling:
1 ½”female
1 ½”female
1 ½”female
1 ½”female
1 ½”female
Degree of protection:
IP 55
IP 55
IP 55
IP 55
IP 55
Protections:
dry running
overload
excess temperature of the electronics
abnormal feeding voltages
(excluding A.D. M/M and A.D. M/T 1.0)
direct short-circuit between the output phases
5.
ELECTRICAL CONNECTIONS OF THE ACTIVE DRIVER TO THE ELECTROPUMP
5.1
Ensure that all the terminals are fully tightened,
paying particular attention to the earth
terminal .
5.2
Check that all the connecting cables are in excellent conditions, with the external sheathing unbroken.
5.3
The motor of the installed electropump must comply with the data in the table in Chapter 4.
The user connected to the ACTIVE DRIVER M/M 1.1 must not exceed 8,5 A as phase current.
The user connected to the ACTIVE DRIVER M/T 1.0 must not exceed 4,7 A as phase current.
The user connected to the ACTIVE DRIVER M/T 2.2 must not exceed 9,3 A as phase current.
The user connected to the ACTIVE DRIVER T/T 3.0 must not exceed 7,5 A as phase current.
The user connected to the ACTIVE DRIVER T/T 5.5 must not exceed 13,3 A as phase current.
5.4
Connect the electropump to the output cable of the ACTIVE DRIVER, paying particular attention to the
earth connection.
The incorrect connection of the earth lines to a terminal other than the earth terminal may
cause irremediable damage to the whole appliance!
The incorrect connection of the power supply line on output terminals intended for the
load may cause irremediable damage to the whole appliance!
6.
CONNECTION TO THE POWER SUPPLY LINE
6.1
Connect the ACTIVE DRIVER to the power supply line by means of the power socket.
(See values in chapter 4).
6.2
If an extension to the power cable is used the following minimum sections must be respected:
Section of each lead (mm²)
Maximum length of the line (metres)
1.5 15
2.5 30
4 60
6.3
If the power cable is extended
FOR THE MOTOR OUTPUT
, for example in supplying submerged
electropumps, in order to comply with the regulations on electromagnetic emission, ensure that the cable is
installed in underground channels (minimum depth 20 cm). If the cable extension exceeds a length of 1.5 metres
out of the ground, connect to mains filters, as indicated in the following table
Mains filters SHAFFNER
Active Driver
Connection
Mains filter IN 25A single-phase
FN 2410-25-33
A.D. = M/M1.1, M/T 1.0, M/T 2.2
Filters to connect
INPUT A.D.
Mains filter IN 50A three-phase
FN 3270H-50-34 A.D. = T/T 3.0, T/T 5.5
Mains filter OUT 10A three-phase
FN 5010-10-99
A.D. = T/T 3.0, M/T 1.0
Filters to connect
OUTPUT A.D.
Mains filter OUT 13A three-phase
FN 5010-13-99
A.D. = M/T 2.2
Mains filter OUT 18A three-phase
FN 5010-18-99
A.D. = T/T 5.5
For correct operation the mains filter must be installed close to the ACTIVE DRIVER!
6.4
The ACTIVE DRIVER is already provided with current protections. If a magnetothermal switch is
installed in line, it must have a max. capacity of 16A.
6.5
The connection of the line to the ACTIVE DRIVER must include the earth line. The total earth resistance
must not exceed 100 Ohm.