10. ACCESS TO MANUAL MODE OF THE MACHINE
(ref. Table no. 14 page 53)
Access keys SET and + and – for 5 seconds
During this phase all the controls and protection systems of the ACTIVE DRIVER are
disabled!
Use of the keys
Keys pressed
Action
SET
and + and – Press them together for a few moments until the display shows MA
+
Increases the frequency and rotation of the electropump
–
Decreases the frequency and rotation of the electropump
MODE
Moves on to the next item in the following menu
FP =
Setting
of the test frequency in manual mode (Hz)
≤
at the set FS value
UP = Display of pressure (bar)
C1 = Display of the electropump phase current (A)
rt =
Setting
of the direction of rotation
UF = Display of flow
ZF = Display of zero flow
MODE
and –
The electropump runs at the set frequency as long as the keys are held down
MODE
and – and
+
(for 2 seconds)
The electropump remains operating at the set frequency.
The electropump may be switched off by pressing
SET
(when
SET
is pressed a second time
it takes you out of the Manual Mode menu).
SET
and –
Changes the direction of rotation of the electropump (active only with the pump running).
SET
Press to stop the electropump or to leave manual mode.
10.1 rt : setting the direction of rotation
In manual mode, irrespective of which heading you are under, you can always invert the direction of
rotation by simultaneously holding down the
SET
and – keys for 2 seconds, this command is active only
with the pump running.
10.2 Starting the electropump .
Pressing the
MODE
and – and + keys simultaneously stops the electropump at the frequency FP.
The running status remains until the
SET
key is pressed.
When the electropump is ON the display blinks quickly.
When the electropump is OFF the display blinks slowly.
In manual mode, pressing the
SET
key takes you out of the menu, but if the electropump has been
started, pressing the key stops only the electropump; when the electropump is stopped, pressing
SET
takes you out of the menu.
11. GENERAL SYSTEM RESET (ref. Table no. 14 page 53)
Access keys MODE and SET and + and –
To restart the appliance without disconnecting the power supply press the 4 keys simultaneously.
MODE and SET and + and –
12. RESTORING THE FACTORY SETTINGS (ref. Table no. 14 page 53)
Access keys SET and +
for 2 seconds when switching on
The factory settings are indicated in table no. 14 on page 53.
To reset the factory values:
Switch off the appliance, press and hold down the
SET
and
+
keys while switching on the appliance again,
release the two keys only when the letters EE appear. In this case the ACTIVE DRIVER restores the factory
settings. When it has finished setting all the parameters the ACTIVE DRIVER returns to normal operation.
In this phase, in the models in which RC is active, the motor current is set at 0 as factory
default, so when you try to start the electropump it will immediately give the error EC. Go to
the installer’s display and settings menu (keys MODE and SET and – for 5 seconds ) and set the
correct motor data plate current (parameter rC as in paragraph 8.5.1.)
13. ERROR AND STATUS CONDITIONS (ref. Table no. 14 page 53)
The ACTIVE DRIVER is equipped with protection systems to preserve the pump, the motor, the
supply line and the ACTIVE DRIVER itself.
If one or more protections trip, the one with the highest priority is immediately notified on the display.
Depending on the type of error the electropump may switch itself off, but when normal conditions are restored
the error status may be cancelled immediately or only after a certain time, following an automatic reset.