Addressable Gas Detection System Manual
Addressable System Manual
76
Issue 2, January 2015
Outputs “Operation Mode”
There are three options for the output Operation Mode
Steady
follows the course of the alarm; alarm activated, output
activated after a possible activation delay; alarm restored,
output low after a possible de-activation delay.
Pulsed
flashing mode with the ON and OFF times adjustable
Timed
single pulse with an adjustable delay activation time and
an adjustable duration time
t
Off
On
activated until the
channel r
the Deactivation Delay
O
u
tp
u
t
s
ta
tu
s
Activation
Delay
0
Output operation mode Steady
Off
On
O
u
tp
u
t
s
ta
tu
s
Output operation mode Pulsed
T1
T1
T2
T2
t
Off
On
O
u
tp
u
t
s
ta
tu
s
0
Output operation mode Timed
T1
T2