Addressable Gas Detection System Manual
Addressable System Manual
36
Issue 2, January 2015
TEST / EXIT TEST
This will put to TEST mode or take out of the TEST (EXIT TEST) mode the selected
channel. It is possible to put in TEST mode just parts of the system when user level
is “Maintenance” or “Engineer”. If more than half of the system is selected, a warning
screen will pop-up.
As far as the number of channels to put in Test/Maintenance mode does not exceed
the defined limits, the selected items will change the status into TEST, as in the
screen below:
Fig. 3.8.4 a) Screen with channels in “Test”
The channels remain in TEST mode until the Channel Maintenance Time set by the
Configuration software (10-60 minutes) is expired.
The EXIT TEST option takes out of the Test/Maintenance mode the selected
channel
In the Channel list (fig. 3.8.4) screen, moving up and down with the arrow keys
through the Detectors list, choose 1 and press ENTER to get into the detector’s
details screen.
This screen is the same for “Operator” and “Maintenance” level, allowing only
viewing the relay configuration details.