Macurco
TM
6/12 Series
Gas Detector and Controller
Installation Manual
Please refer to Product Operation Manual for additional product information and
features.
NOTE: Read and understand the User Instructions before installing and operating
this product. Refer to page 7 to access the User Instructions.
1.
Safety
Installation must comply with recognized standards of the appropriate authority
in the country and concerned locality.
2.
Use Instructions and Specifications
NOTE
: Macurco 6/12 Series detector are not intended for use in hazardous
locations. Please refer to product full operating instructions for details on
application of each detector.
Product
Gas Detected
(Range)
CM-xx
Carbon Monoxide (CO)
0-200 ppm
TX-xx-ND
Nitrogen Dioxide (NO2)
0-20 ppm
GD-xx
Combustible (Default: Methane)
0-50 %LEL
TX-xx-AM
Ammonia (NH3)
0-100 ppm
TX-xx-HS
Hydrogen Sulfide (HS)
0-50 ppm
RD-xx
Refrigerant (REF)
0-1000ppm
OX-xx
Oxygen (O2)
0-25% vol
CD-xx H/MC
Carbon Dioxide (CO2)
0-5000 ppm
CD-6B
Carbon Dioxide (CO2)
0-5.00% vol
CD-6G
Carbon Dioxide (CO2)
0-5.00% vol
CX-xx
Carbon Monoxide and Nitrogen
Dioxide
CO: 0-200 ppm
NO2: 0-20 ppm
xx – 6 (for low voltage detector) or 12 (for line voltage detector)
ETL LISTED to UL 61010-1, Certified to CSA C22.2#61010-1
To access the complete manual, go to
or scan the code
below:
Macurco Gas Detection
3601 N. St. Paul Avenue
Sioux Falls, SD 57104
Technical Support Contact Information
Phone: 1-844-325-3050
Fax : 605-951-9616
Email:
Website:
General Contact Information
Phone: 1-877-367-7891
Fax: 605-951-9616
Email:
Web site:
Rev – 1.1
Issue Date: 12-09-2020
Document No: 34-2900-0513-8
© Aerionics 2019. All rights reserved.
Macurco is a trademark of Aerionics, Inc.
Specifications
Dimensions
4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
Shipping weight
1 pound (0.45 kg)
Color
White or Dark Gray
Power Supply
Input voltage
and Power
6-series: 12 to 32 VDC or 12 to 24 VAC (Max Power: 3W)
12-series: 100-240 VAC (50 to 60 Hz), 1.0A Max Current
Operating Environment
Temperature
0
o
F to 125
o
F
32°F to 122°F (for CD-xxH/MC, CD-6B only)
Humidity and
Atmospheric Pressure
10 to 90% RH non-condensing *
0 to 85% RH non-condensing**
1 atm ± 20% (for CD-6B only)
Installation
Connections
plugs/terminals
Mounting box
4x4 electric (not included)
Features
Digital display
4-digit LED configurable to OFF or ON (not configurable
for RD-6/12)
Buzzer
85 dBA at 10cm selectable to off or on (default)
*Alarm Relay
0.5A, 120 VAC
*Fan Relay
5A, 240 VAC, SPDT
**Alarm 1 and 2 Relay
SPST to switch 2.0A load, up to 240 VAC or 30 VDC
**Alarm 3 Relay
SPDT to switch 2.0A load, up to 240 VAC or 30 VDC
*
All models except CD-6B.
**CD-6B only
3.
Installation
Refer to product manual for coverage of the detector and installation location.
NOTE
: De-energize Power during installation and wiring. Use 12 to 22 AWG wire.
Mounting
- The device mounts on a 4” square (or 4x4) electrical box. Do not
mount the device inside another box, unless it has good air flow through it.
Power Supply
- Use Class 2 power supply only for 6-series. Power connector does
not have polarity preference
.
•
Connect the device to the control cables with terminal plugs. Connect the
cable to corresponding terminal modular connector (refer to Figure 1 and
2).
•
For 4-20mA connection, connect the wire to appropriate polarity.
•
Relay connectors labeled ‘A’ and ‘B’ can be configured to normally open
(NO) or normally closed (NC) via configuration menu.
•
For Relay Connectors labeled ‘NC’, ‘COM’ and ‘NO’, NC refers to normally
closed, COM refers to common, and NO refers to normally open.
Figure 1 Low Voltage Detector (6 Series) Rear View and Connectors
Figure 2 Line Voltage Detector (12 Series) Rear View and Connectors
NOTE:
The safety of any system incorporating the equipment is the responsibility
of the installer of the system.
4.
Operations
NOTE: Refer to product User Instructions to get additional details on product
feature and operation.
Power Up
– Macurco 6/12 Series detector will execute a self-test cycle any time
power is dropped and reapplied (i.e. power failure). During the test, the indicator
LED will flash green and count down is displayed. After countdown is over, the
indicator LED will turn solid green and the detector is ready for use.
Status Indicator
- From
lowest
to
highest
, the alarm priority is as follows:
Awareness Alarm, Alarm 1, Alarm 2, Alarm 3, Trouble Fault.
The following alarm behavior is observed with the default settings (display “On”,
buzzer “On”)
1
:
•
Clean Air
–The device will show the current gas concentration.
1
•
Alarm Level
– When the gas concentration is beyond the alarm level
threshold, the corresponding alarm relay will engage and the display will
flash between ‘ALr’ (‘ALrX’ for CD-6B ,where X is 1,2 and 3 for Alarm 1, 2
and 3 respectively) and current gas reading, and buzzer will beep every
second.
1
•
Trouble
– If the detector is in a trouble state, the “t” Error code will be
displayed (t01, for example). The green status indicator LED light will flash,
and the buzzer will beep intermittently. If the Trouble Condition setting is
enabled (default is “OFF”), Alarm Relay (Alarm 1 Relay for CD-6B) will
activate.
•
Calibration Due
– If the device is within 1 month of calibration period and
Calibration Period functionality is enabled, then the display will flash
between “dUE” and current gas concentration. Calibration Due is resolved
only with a successful field calibration.
2
1
RD-6 does not display gas readings and does not has display configuration
settings.
2
Calibration Due features might not be available on all Macurco detectors.
Change Settings
- To change settings, remove the Philips screw on the front of
the detector. Pull off the front cover of the unit. Locate the MENU/NEXT and
ENTER/TEST buttons.
To change a setting, in normal mode:
1.
Push the
Next
button to get to “Con” (Configuration) menu.
2.
Push the
Enter
button to enter the Con menu.
3.
Push the
Next
button until the desired setting is visible.
4.
Push
Enter
.
5.
Push
Next
to cycle through available options.
6.
Push
Enter
to confirm the change.
7.
Push
Enter
again to return to the Con menu.
8.
Push
Next
until “End” is displayed.
9.
Push
Enter
to get back to normal operation.
For a complete list of available settings, refer to the complete User Instructions.
* All models except CD-6B
**CD-6B only
*
**
**
*