 6/12 Series 

Gas Detector and Controller 

Installation Manual 

 

Please refer to Product Operation Manual for additional product information and 

features.  
NOTE: Read and understand the User Instructions before installing and operating 

this product. Refer to page 7 to access the User Instructions. 

1.

 

Safety 

Installation must comply with recognized standards of the appropriate authority 

in the country and concerned locality. 

2.

 

Use Instructions and Specifications 

NOTE

: Macurco 6/12 Series detector are not intended for use in hazardous 

locations. Please refer to product full operating instructions for details on 

application of each detector. 

 

Product 

Gas Detected  

(Range) 

CM-xx 

Carbon Monoxide (CO) 

0-200 ppm 

TX-xx-ND 

Nitrogen Dioxide (NO2) 

0-20 ppm 

GD-xx 

Combustible (Default: Methane) 

0-50 %LEL 

TX-xx-AM 

Ammonia (NH3) 

0-100 ppm 

TX-xx-HS 

Hydrogen Sulfide (HS) 

0-50 ppm 

RD-xx 

Refrigerant (REF) 

0-1000ppm 

OX-xx 

Oxygen (O2) 

0-25% vol 

CD-xx H/MC 

Carbon Dioxide (CO2) 

0-5000 ppm 

CD-6B 

Carbon Dioxide (CO2) 

0-5.00% vol 

CD-6G 

Carbon Dioxide (CO2) 

0-5.00% vol 

CX-xx 

Carbon Monoxide and Nitrogen 

Dioxide 

CO: 0-200 ppm 

NO2: 0-20 ppm 

xx – 6 (for low voltage detector) or 12 (for line voltage detector) 

 

ETL LISTED to UL 61010-1, Certified to CSA C22.2#61010-1 

 

To access the complete manual, go t

www.macurco.com

 or scan the code 

below:

 

 

  

 

Macurco Gas Detection

 

3601 N. St. Paul Avenue 

Sioux Falls, SD 57104 

Technical Support Contact Information

 

Phone: 1-844-325-3050 

Fax : 605-951-9616 

Email: 

[email protected]

  

Website: 

www.macurco.com/support/ 

General Contact Information

 

Phone: 1-877-367-7891 

Fax: 605-951-9616  

Email: 

[email protected]

  

Web site

www.macurco.com

 

 

Rev – 1.1 

Issue Date: 12-09-2020 

Document No: 34-2900-0513-8 

© Aerionics 2019. All rights reserved.  

Macurco is a trademark of Aerionics, Inc. 

 

 

 

 

Specifications 

Dimensions 

4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm) 

Shipping weight 

1 pound (0.45 kg) 

Color 

White or Dark Gray 

Power Supply 

Input voltage 

 

and Power 

6-series: 12 to 32 VDC or 12 to 24 VAC (Max Power: 3W) 

12-series: 100-240 VAC (50 to 60 Hz), 1.0A Max Current 

Operating Environment 

Temperature 

0

o

F to 125

o

F  

32°F to 122°F (for CD-xxH/MC, CD-6B only) 

Humidity and 

Atmospheric Pressure 

10 to 90% RH non-condensing * 

0 to 85% RH non-condensing** 

1 atm ± 20% (for CD-6B only) 

Installation 

Connections 

plugs/terminals 

Mounting box 

4x4 electric (not included) 

Features 

Digital display 

4-digit LED configurable to OFF or ON (not configurable 

for RD-6/12) 

Buzzer 

85 dBA at 10cm selectable to off or on (default) 

*Alarm Relay 

0.5A, 120 VAC 

*Fan Relay 

5A, 240 VAC, SPDT 

**Alarm 1 and 2 Relay 

SPST to switch 2.0A load, up to 240 VAC or 30 VDC 

**Alarm 3 Relay 

SPDT to switch 2.0A load, up to 240 VAC or 30 VDC 

*

All models except CD-6B. 

**CD-6B only 

 

3.

 

Installation 

Refer to product manual for coverage of the detector and installation location. 

NOTE

: De-energize Power during installation and wiring. Use 12 to 22 AWG wire. 

Mounting

 - The device mounts on a 4” square (or 4x4) electrical box. Do not 

mount the device inside another box, unless it has good air flow through it.  

Power Supply

 - Use Class 2 power supply only for 6-series. Power connector does 

not have polarity preference

 

Connect the device to the control cables with terminal plugs. Connect the 

cable to corresponding terminal modular connector (refer to Figure 1 and 

2).  

 

For 4-20mA connection, connect the wire to appropriate polarity. 

 

Relay connectors labeled ‘A’ and ‘B’ can be configured to normally open 

(NO) or normally closed (NC) via configuration menu. 

 

For Relay Connectors labeled ‘NC’, ‘COM’ and ‘NO’, NC refers to normally 

closed, COM refers to common, and NO refers to normally open. 

 

 

 

Figure 1 Low Voltage Detector (6 Series) Rear View and Connectors 

 

 

Figure 2 Line Voltage Detector (12 Series) Rear View and Connectors 

 
NOTE:

 The safety of any system incorporating the equipment is the responsibility 

of the installer of the system. 

 

4.

 

Operations 

NOTE: Refer to product User Instructions to get additional details on product 

feature and operation. 

Power Up 

– Macurco 6/12 Series detector will execute a self-test cycle any time 

power is dropped and reapplied (i.e. power failure). During the test, the indicator 

LED will flash green and count down is displayed. After countdown is over, the 

indicator LED will turn solid green and the detector is ready for use. 

Status Indicator 

- From 

lowest

 to 

highest

, the alarm priority is as follows: 

Awareness Alarm, Alarm 1, Alarm 2, Alarm 3, Trouble Fault. 

The following alarm behavior is observed with the default settings (display “On”, 

buzzer “On”)

1

:  

 

Clean Air

 –The device will show the current gas concentration.

1

  

 

Alarm Level

 – When the gas concentration is beyond the alarm level 

threshold, the corresponding alarm relay will engage and the display will 

flash between ‘ALr’ (‘ALrX’ for CD-6B ,where X is 1,2 and 3 for Alarm 1, 2 

and 3 respectively) and current gas reading, and buzzer will beep every 

second.

1

 

 

Trouble

 – If the detector is in a trouble state, the “t” Error code will be 

displayed (t01, for example). The green status indicator LED light will flash, 

and the buzzer will beep intermittently. If the Trouble Condition setting is 

enabled (default is “OFF”), Alarm Relay (Alarm 1 Relay for CD-6B) will 

activate. 

 

Calibration Due

 – If the device is within 1 month of calibration period and 

Calibration Period functionality is enabled, then the display will flash 

between “dUE” and current gas concentration. Calibration Due is resolved 

only with a successful field calibration.

2

 

RD-6 does not display gas readings and does not has display configuration 

settings.

 

Calibration Due features might not be available on all Macurco detectors.

 

Change Settings 

- To change settings, remove the Philips screw on the front of 

the detector. Pull off the front cover of the unit. Locate the MENU/NEXT and 

ENTER/TEST buttons. 
To change a setting, in normal mode:  

1.

 

Push the 

Next

 button to get to “Con” (Configuration) menu. 

2.

 

Push the 

Enter

 button to enter the Con menu.  

3.

 

Push the 

Next

 button until the desired setting is visible. 

4.

 

Push 

Enter

5.

 

Push 

Next

 to cycle through available options. 

6.

 

Push 

Enter

 to confirm the change. 

7.

 

Push 

Enter

 again to return to the Con menu. 

8.

 

Push 

Next

 until “End” is displayed. 

9.

 

Push 

Enter

 to get back to normal operation. 

For a complete list of available settings, refer to the complete User Instructions. 
 
 

* All models except CD-6B 

**CD-6B only 

 

** 

** 