Fault Descriptions
Flash Invalid
This fault indicates that the firmware checksum has failed. Use the Tools Program Flash menu item from PowerTools to
reprogram/upgrade the firmware stored in flash memory. If this problem persists, call Control Techniques. A common cause
would be an interrupted F/W Flash upgrade (cable disconnected during an upgrade process).
Power Up Test
This fault indicates that the power-up self-test has failed. This fault cannot be reset with the reset command or reset button.
NVM Invalid
At power-up the drive tests the integrity of the non-volatile memory. This fault is generated if the contents of the non-volatile
memory are invalid.
Encoder State
Cycle Power
Yes
Encoder Hardware
Cycle Power
Yes
Motor Overtemp
Reset Button or Input Line
Yes
RMS Shunt Power
Reset Button or Input Line
Yes
Overspeed
Reset Button or Input Line
Yes
Max Following Error
Reset Button or Input Line
Yes
Travel Limit +/-
Auto
No
All "On"
Normally on for one second during
power up
Yes
Run Time Faults
Reset Button or Input Line
Yes
Drive Overtemp
Allow the drive to cool down,
Cycle Logic Power
Yes
Segment
Display
Fault
Action to Reset
Bridge
Disabled
Summary of Contents for Epsilon EP-P
Page 2: ......
Page 124: ...110 Epsilon EP P Drive Reference Manual www controltechniques com Revision A4...
Page 200: ...186 Epsilon EP P Drive Reference Manual www controltechniques com Revision A4...
Page 218: ...204 Epsilon EP P Drive Reference Manual www controltechniques com Revision A4...
Page 238: ...224 Epsilon EP P Drive Reference Manual www controltechniques com Revision A4...
Page 244: ...230 Epsilon EP P Drive Reference Manual www controltechniques com Revision A4...
Page 247: ......