23
Operator Interface
Nortec GS
2583701_C_EN_1812_Nortec-GS_OM
–
Blowdown Rate:
shows the rate at which the tank is partially
drained, as a percentage of actual steam production. Refer to the
"Water Management Tab" on page 25
–
Drain Cool:
shows the configuration setting of the drain cool function.
Select the field to choose a different mode – "Off", "On" or "Smart".
Refer to the
"Water Management Tab" on page 25
for more details.
–
Float Check:
shows the configuration setting of the float check func
-
tion. Select the field to enable or disable the function. Refer to the
for more details.
–
Float Check Time:
allows you to see and set the time of day when
the float check function will occur.
–
FTBD (Full Tank Blowdown):
shows the configuration setting of
the full tank blowdown function. Select the field to enable or disable
"Water Management Tab" on page 25
for more
details.
–
FTBD Interval:
shows how often a full tank blowdown will occur.
Refer to the
"Water Management Tab" on page 25
for more details.
–
FTBD Time:
shows the time of day when a full tank blowdown will oc
-
cur. Refer to the
"Water Management Tab" on page 25
–
Time Proportioning:
shows the configuration setting of the time pro
-
portioning function. Select the field to enable or disable the function.
Refer to the
for more details.
–
Idle Mode:
allows you to set the idle function of the humidifier when it
is in standby mode.
–
Idle Drain Time:
allows you to set the time duration the humidifier
stays in standby mode without a demand, after which the humidifier
carries out the function specified in
Idle Mode
.
–
Short Cycle:
allows you to enable or disable a timer function that
delays steam production until the already delivered humidity can
stabilize in the conditioned environment. This feature prevents the
humidifier from flooding the environment with excess humidity from
false humidity readings.
–
Short Cycle Time:
allows you to set the time duration that the unit
waits in standby mode before responding to a new demand signal.
Networking Settings Tab
–
Modbus:
shows if Modbus communication is enabled.
–
Modbus Address:
shows the Modbus address.
–
BACnet MSTP MAC:
shows the MAC address assigned to the
humidifier.
–
IP Address:
shows the IP address assigned to the humidifier.