73
Fault Isolation
Nortec GS
2583701_C_EN_1812_Nortec-GS_OM
Code
Message
Probable Cause
Corrective Action(s)
Warning
Fault
W32
–
RH Signal
The RH input is less than 3%. Operation is interrupted until an input higher
than 3% is received.
Loose wiring, faulty sensor.
– Check the connection between
the sensor and the unit.
– Swap the sensor with another
sensor and verify that it is work
-
ing. If necessary, replace the
sensor.
Layout of the humidifier control sys
-
tem may be causing signal interfer
-
ence.
– Check that the controls layout
permits accurate readings.
W34
–
Remote Disabled
The unit has been disabled remotely by the building management system
(BMS) through Modbus communication. Operation is interrupted until the
unit is enabled again through Modbus or the control software.
Unit disabled through the BMS.
– Enable the unit through the
BMS.
– If unit cannot be enabled
remotely, try enabling the unit
through the
control software.
W35
–
BMS T/O (timeout)
The maximum wait time without any communications from the BMS has
been exceeded. If the signal
is set to "Analog", the humidifier will
continue operating; otherwise it stops producing steam until communica
-
tions with the BMS is re-established.
W42
–
RH High Warning
value configured in the control soft
-
ware. The unit will remain idle until the sensed RH value drops below the
setpoint value.
Incorrect layout of the humidifier
control system (sensor location too
close to steam distributor or other
sources that affect measurement), or
defective components.
– Check the humidifier control
system.
Humidifier capacity too large for the
space being humidified.
– Limit the output capacity of
of the controller.
value for the sensor
signal may be set too low.
– Adjust the RH High value for the
sensor signal.
W43
–
RH Low Warning
Sensed humidity is below the minimum value configured in the control soft
-
ware. The unit should continue operating unless it is in standby mode.
Incorrect layout of the humidifier
control system (sensor location too
close to steam distributor or other
sources that affect measurement), or
defective components.
– Check the humidifier control
system.
value for the sensor
signal may be set too high.
– Adjust the RH Low value for the
sensor signal.
Unit may be in standby mode.
– Check the safety loop is
closed, and that all burners are
operational.