37
Operator Interface
Nortec GS
2583701_C_EN_1812_Nortec-GS_OM
Nortec Online Tab
–
Nortec Online:
provides web-based remote monitoring. This
operation operates in conjunction with a server at Condair's facili
-
ties and allows the user to monitor and control various aspects of
humidifier operation, such as diagnostics and trend data, and send
email notifications for service/fault warnings.
Options:
Enabled
– connects to Nortec Online
.
Disabled
– prevents connection to Nortec Online
–
Online Status:
shows the current connection status to Nortec Online
–
PIN:
shows the PIN generated by the server. The PIN is required to
register the unit on the Nortec Online server.
–
Serial Number:
shows the serial number of the humidifier (that
was registered online)
–
JID:
shows the Jabber ID of the humidifier. This ID is used by the
server to identify the humidifier.
Network Time
(available when Nortec Online is enabled)
–
Time Zone:
Sets the time zone the humidifier is installed in, and
the interval Nortec Online will use to check the current time.
Range:
0-0
Factory setting:
6
–
Update Interval:
Set the time for logging events on the Nortec
Online server.
Range:
1-
120 min
Factory setting:
60 min
Remote Fault Board
–
Indication:
Alters how system warnings are generated on the
remote fault board. If warning is selected the RFB will activate the
service output on any system warning, including system notifica
-
tions prior to completing automated corrective actions (ex. fill time
-
out). If Service is selected, the RFB will activate the service output
only for service warnings.
Options:
Warning, Service
Factory setting:
Warning
–
Safety Loop:
when enabled the remote fault board will activate the
service relay upon the security loop opening
Options:
Yes, No
Factory setting:
No