25
Operator Interface
Nortec GS
2583701_C_EN_1812_Nortec-GS_OM
Features Menu
Each tab under the Features menu is discussed below.
Water Management Tab
–
Idle Mode:
allows you to set the idle function of the humidifier
when it is in standby mode.
Options:
Idle Only
– the humidifier waits indefinitely
for a demand signal.
Idle Drain
elapses without demand.
Keep Warm
– the water in the tank is kept
warm while in standby mode.
Factory setting:
Idle Drain
–
Idle Drain Time:
allows you to set the time duration the humidifier
stays in standby mode without a demand, after which the humidi
-
fier carries out the function specified in
.
Setting range:
1-100 hours
Factory setting:
72 hours
–
Float Check:
allows you to enable or disable the float check func
-
tion. When enabled, the humidifier performs a float check at start-
up and every 24 hours (without interrupting steam production if
humidifier is operating, or in standby mode), to verify that the float
system is working properly. .
Options:
On or Off
Factory setting:
On
–
Float Check Time:
allows you to set the time of day when the float
check function will occur.
–
Blowdown Rate:
allows you to set the rate (as a percentage of
actual steam production) at which the tank is drained. Refer to
"Adjusting Blowdown Settings" on page 53
Setting range:
1-50%
Factory setting:
25%
–
Drain Cool:
allows you to enable or disable the drain water cooling
function that is used to cool down the drain water before it is discharged.
Options:
On
– enable the function.
Off
– disable the function.
Smart
– drain water cooling happens only if
the tank is hot.
Factory setting:
On
–
DWC (Drain Water Cooling) Source:
allows you to select the
water source used in drain water cooling.
Options:
Internal
– use the fill valve in the unit to sup
-
ply water for drain water cooling setting:
Internal