AlphaServer 8400 System
3
-
3
The values in Table 3-1 apply to the 8400 system cabinet only. The values are
configuration dependent. Additional options will increase electrical requirements so
that an additional power regulator may be needed.
Table 3-1 Electrical Characteristics
Electrical
Specification
3-phase AC input voltage
(current, maximum)
120/208 V Wye (30A) – North America
380–415 V Wye (30 A) – Europe/AP
202 V Delta (16 A) – Japan
Nominal Frequency
50–60 Hz
AC power consumption
(maximum)
4.6 KW
Table 3-2 Environmental Characteristics
Environmental
Operating
Storage
Heat dissipation
15,700 Btu/hr
–
Temperature¹
15º–28º C (59º–82º F)
-40º–66º C (-40º–151º F)
Relative humidity
x
20–80%
10–95%
Altitude
0–2.4 km (0–8200 ft)
0–9.1 km (0–30,000 ft)
¹
Recommended operating temperature is 18º–24º C (65º–75º F) and 40–60% relative humidity.