Install and Connect the Subrack Cards
.
Connect the SUI Card
The SUI Card allows you to connect the WCS Subrack to a local laptop, LAN, or modem. Connect any of these
devices as required for local practice.
•
Local:
Use Ethernet CAT 5 cable (straight or crossover) with RJ-45 connectors to connect a local laptop
or PC to the Local port to allow for administration of the ERA system through the ERA software.
•
LAN2:
Use Ethernet CAT 5 cable (straight or crossover) with RJ-45 connectors to connect your LAN or a
modem to the LAN2 port.
To maximize airflow through the WCS and e-POI chassis, blank panels must be installed in all empty slots.
If additional blank panels are required, contact your local CommScope sales representative to order the
appropriate panel:
• ERA Blank Panel Universal (PN 7688866-xx)
• ERA Blank Panel SUI (PN 7688868-xx)
• ERA Blank Panel AUT (PN 7688867-xx).
CDD Cards and RFD Cards should be populated in the Subrack from bottom to top starting with the
bottom slot of each section of the Subrack (Slot R1 or Slot R5) to ensure optimal airflow to the cards.
The LAN1 port is not currently used.
The USB port is reserved for use by CommScope.
SUI Cards are hot swappable; you do not need to power down the CAN, TEN, or WIN to install or remove
an SUI Card.