7. Appendices
Appendix A: Error messages shown on the 41CPE118 fire alarm panel display:
Message text
Description
Alarm
Common Fire Alarm
Loop Device Type Error
A different type of device than the specified type has been found at the address.
Loop Device Fault
The device is not responding (removed or faulty).
Double Address
Devices with the same address are present on the Loop.
PreAlarm
Fire alarm originating from a sensor/button for a zone set as “2 Devices” or “Double
alarm”.
Evacuate
Manual button activated, or the “Evacuate” panel button.
Loop Device Input Fault
Fault at the input of a Loop device.
Loop Device Output Fault
Fault at the output of a Loop device.
Loop Device Sounder-Fault
Sounder on Loop faulty (short-circuit or line opened).
Fault Output - Fault
Fault at the panel fault output (short-circuit or line opened).
Fire Brigade - Fault
Fault at the panel Fire Brigade output (short-circuit or line opened).
Fire Protection - Fault
Fault at the panel Fire Protection output (short-circuit or line opened).
Loop Device Disabled
A Loop device has been disabled.
Chamber Fault
Sensor chamber photodiode fault.
Clean Me Now
Photodiode inside the sensor chamber dirty.
TEST ALARM
Alarm originating from a sensor for a zone in Test mode.
Signal Blockage
Signal inhibited at the linear barrier.
Hi Signal
Signal too high from the linear barrier.
Drift Alert
Balancing threshold reached in the sensor.
Earth Fault
Dispersion to earth < 10k.
Battery Low
Panel battery low.
Charger Fault
Fault in the battery recharging circuit.
Battery Loss
Panel battery loss.
AC Loss
230 V main power supply loss.
Sounder Fault
Fault at the panel sounder output (short-circuit or line opened).
AUX 24V Fault
Short-circuit (no power) at the AUX 24V output.
AUX 12V Fault
Short-circuit (no power).
Periphery Device Fault
A periphery device is not responding (removed or faulty).
Periphery Device Type Error
A different type of device than the specified type has been found at the address.
External Power Supply Fault
Problem with the external power supply (battery low, battery loss, charger fault,
main power supply loss or dispersion to earth).
External Power Supply Loss
There is an external power supply loss.
Zone Disabled
The zone is disabled.
Zone In Test
The zone is in test mode.
Sounder Disabled
The Sounder output has been disabled.
Fire Brigade Output Disabled
The Fire Brigade output has been disabled.
Fire Protection Output Disabled
The Fire Protection output has been disabled.
Fault Output Disabled
The Fault output has been disabled.
Reset
The control panel has been reset.
Silence Alarm
The sounders have been silenced.
Ram Error
Error in RAM.
Flash Error
Error in permanent storage.
Panel Fault
Connection with the other panel interrupted (when two or more panels are
connected in a network).
Double IP address
Panel IP address duplicated.
Double Panel number
Panel number duplicated (when two or more panels are connected in a network).
88