41SCB100 – Base with built-in sounder and strobe and isolator
17/06/2020 14:06
41SCB100
Address
Loop Number
Device Zone
15
2
1
Enabled
Normal
Device State
More
Remove
OFF
Name
17/06/2020 14:06
Sound/Strobe
High
Mode
Sound Level
Software Revision
ID
2.0
3195011485
0
Sounder Group
The figure shows the settings screen for addressed sounder/strobe 41SCB100.
Press “MORE” to access additional settings:
•
Mode
: press the button to change the sounder operating mode; choose between:
◊ Strobe lamp - in the event of activation, only the visual part of the sounder is enabled
◊ Sounder – in the event of activation, only the audible part of the sounder is enabled
◊ Sound/Strobe – in the event of activation, both visual and audible parts of the sounder are enabled
•
Sound Level
: on pressing the button, the sound level alternates between HIGH and LOW - this setting can be determined
by the total number of sounders connected to the Loop:
◊ High - Set for cases in which the number of sounders connected to a single Loop is ≤ 30.
◊ Low - Set for cases in which the number of sounders connected to a single Loop is between 30 and 100.
•
Sounder Group
: each addressed Comelit sounder can belong to a Sounder Group. In the event of a zone alarm, in addition
to the sounders belonging to that zone, the sounder groups associated with that zone will also be activated.
To save any new parameters, press “Save” on the main device screen.
Note: the detectors mounted on bases 41SAB100 and 41SCB100 will be assigned another address which is NOT the
same as the base.
CAUTION: disabling sounders is not compliant with standard EN54-2!
If a sounder is disabled, a warning message will appear on the screen.
Disabling a base with sounder (models 41SAB100 and 41SCB100) will not affect operation of the addressed detector mounted
on it.
To calculate the total consumption of the sounders in the loop and their sound level, use the table below, entering the number
of sounders used and calculating their total consumption.
Sounder
Number
High Volume
Low Volume
Maximum Consumption, mA (High +
Low)
41SAI000
_____ x 10 mA
_____ x 4 mA
41SCI000*
_____ x 16.5 mA
_____ x 11 mA
41SAB100
_____ x 10 mA
_____ x 3 mA
41SCB100
_____ x 10 mA
_____ x 3 mA
Total consumption of the sounders in the loop:
Table 1
Calculation of the total consumption of the sounders in the loop: