4.7.3 Disablements menu
This submenu allows the installer to enable or disable the following indications:
•
Earth Fault
•
Battery High Resistance
•
Internal Buzzer
17/06/2020 14:06
Earth Fault
Battery High Resistance
Internal Buzzer
Enabled
Disabled
Disabled
CAUTION: the “Battery High Resistance” indication must be enabled in compliance with standard EN54-4!
On initial panel startup, the “Battery High Resistance” indication is disabled and must be enabled by the
installer. Every time the panel is restarted (main and backup power supply disconnected), the “Battery High
Resistance” indication is disabled and must be enabled by the installer.
After completing the changes, press “Save”.
4.7.4 Sounders Mode
This submenu gives the installer the option of setting and changing the parameters common to all sounders on the Loop within
the system.
17/06/2020 14:06
970Hz
Evacuation Tone
800Hz - 970Hz @ 1Hz
Alarm Tone
0
Evacuation Timeout (T3)
Enabled
Resound Alarm
Sounders Mode
1
More
Common
3
970Hz, 0.5s ON / 0.5s OFF x 3
Class change tone
11
17/06/2020 14:06
Alert/EVAC voice cycles ON
Alert/EVAC voice cycles OFF
NORMAL
Alert/EVAC voice cycles
Evacuation settings
Strobe lamp
0
0
Alarm settings
Individual
EVAC Zones
The following parameters can be changed:
•
Sounders Mode
: press the button to change the sounder operating mode:
◊
Common
– in fire alarm condition, all sounders will be activated regardless of the zone to which they belong;
◊
Zonal
– in fire alarm condition, only the sounders belonging to the zone for which the alarm was triggered will be
activated;
•
Resound Alarm
: this field is enabled in both operating modes (Zonal and Common). When this option is disabled, after
the sounders are silenced for the first time (Silence Alarm button pressed), they will no longer be reactivated if a second
Fire Alarm event occurs; they can only be activated manually. When the option is Enabled, the silenced sounders will be
activated automatically if a second Alarm event occurs.
•
Evacuation Timeout (T3)
: this is the delay time when actual site evacuation begins. You can enter a delay from
1 to 10 minutes. If the value = 0, the panel will never enter Evacuate mode (automatic).
•
Alarm Tone
: field used to change the sounder tone when they are in Fire Alarm condition. Buttons
+ & -
can be used to
select one of the 32 available tones. By default the Alarm tone in the panel is number 3
(800Hz-970Hz @ 1Hz).
•
Evacuation Tone
: field used to change the sounder tone when they are in Evacuate condition. Buttons
+ & -
can be used
to select one of the 32 available tones. By default the Evacuate tone in the panel is number 1
(970Hz continuous).
•
Class change tone
: field used to change the sounder tone when they are in class change mode (970Hz, 0.5s ON / 0.5s
OFF x3)
68