The panel automatically shows the first address in the system. Use the + & - buttons to select the address and the loop
number you want to change. In the “New Address” field, set the new address number for the device. If the address is free, the
“Save” button will appear on the screen.
To change the address, press “Save” and wait a couple of seconds. If the address was changed successfully, the message
“Successful” will appear on the screen. You can proceed with changing another address or exit using the
17/06/2020 14:06
Reset
Outputs
OFF
Set Address
Address
Loop Number
17
1
41SCB100
button.
You can use the “RESET” button to reset the device operating conditions. The “Outputs” button is only active for modules with
outputs or sounders. Use the “Outputs” button to enable or disable the module outputs / sound part of the sounder.
4.3.3.2 Changing an address
The installer can use this submenu to change the address of a device. To change an address, select the following sequence:
SYSTEM – PROGRAMMING - DEVICES – ADDRESSING - CHANGE ADDRESS.
17/06/2020 14:06
Reset
Outputs
OFF
Change Address
Address
Loop Number
1
2
41PAM000
New Address
1
4.4 Zones
To access the zone programming menu, select the following sequence:
SYSTEM – PROGRAMMING – ZONES
Addressed panel 41CPE118 has 500 zones. The FIRE ALARM and PREALARM statuses are shown on the front cover, through
the activation of the corresponding LED (up to 200). In the PREALARM condition, the corresponding zonal LED flashes and an
alert message is shown on the panel display.
If a device is activated in the same zone for a second time, a FIRE
ALARM message is generated for the relevant zone; the number of the zone in fire alarm mode lights up in red.
17/06/2020 14:06
Zone Number
More
60
1
Save
Zone Status
Mode
Sounder Delay (T2)
Fire Brigade Delay (T2)
Fire Protection Delay (T2)
Name
60
Enable
0
Double
Zone Group
17/06/2020 14:06
Zone Number
0
1
Zone sounders
Sounder group
Sounder group
Sounder group
0
Enable
0
The figure shows the general screen for programming a Zone.
49