CAUTION: If auto addressing via isolator, make sure that all devices installed on the Loop have an
isolator. The only Comelit device which does NOT have an isolator is mini module 41IOM010. If starting
this addressing procedure and modules 41IOM010 have been installed on the Loop, the search will not
be successful and will stop as soon as the panel detects one of these devices. Repeat the addressing
procedure using another method.
17/06/2020 14:06
Autoaddressing
Loop Number
Number of Devices
2
0
Start Autoaddressing ID
Start Autoaddressing Isolator
Status
More
17/06/2020 14:06
Branch
Address
Number of devices
1
5-6
2
The figure shows the auto addressing menu screen. Press “More” to view, if present, the number of branches on the Loop and
the addresses that are part of it.
CAUTION: on carrying out one of these 2 auto addressing procedures on a 41CPE118 fire panel that is
already operative (devices already addressed), all devices will be re-addressed according to the new
procedure selected, with the risk that their numerical sequence and therefore the associated operating
logics will be changed!
To access the addressing menu, carry out the sequence below:
SYSTEM – PROGRAMMING – DEVICES – ADDRESSING
17/06/2020 14:06
Set Address
Change Address
Start Self Addressing
Autoaddressing
Loop zero address
During any of the addressing procedures, panel 41CPE118 enters a special operating mode for the addressing of devices: the
panel is busy and does not check the operation of the other devices in the system. The menus for reviewing alarms, faults,
warnings, tests and disabling procedures are temporarily disabled.