17/06/2020 14:06
41IOM122
1
Loop device address
1
Loop number
Loop device output parameters
3
Channel (3,4)
LOOP
: select this option when the output is an output module terminal.
Press “MORE” to program the following parameters:
◊
Loop device address
: enter the device address.
◊
Loop number
: enter the number of the loop to which the device belongs.
◊
Channel
: enter the channel number for the device you want to enable. The channels available for the selected device are
shown in brackets.
CAUTION: If the device is a sounder, or a conventional zone module 41ISC000, the panel will only show one
available channel.
The following alert messages may be shown on the screen:
• “
This device can not be used as Output!
” - This means that the set device or channel cannot be used as an output.
The message is shown if the set address is for a device type that does not have programmable outputs (e.g. input-only
modules).
• "
Already Used!
" - This means that the set device or channel is already being used for other procedures in the panel
configuration.
To save any new parameters, press “Save” on the main input screen.
•
NETWORK
: select this option when the output needs to be reported to the (network) input of another panel connected via
RS485 / LAN.
17/06/2020 14:06
Network output parameters
0
Input number
0
anrel / repeater number
Press “MORE” to set:
•
Input number
: enter the input number, between 1 and 250.
•
Panel / repeater number
: enter the number of the panel from which the network input originates, between 1 and 64.
To save any new parameters, press “Save” on the main input screen.
62