4.6.2 Edit Outputs Map menu (entering input groups and checking the outputs)
Menu for programming logic procedures for output enabling. The map is individual and can be set for every single output.
Logic interactions such as inputs checking the outputs are set on a map which is shown on a separate screen after the Edit
Outputs Map has been pressed in the main Outputs menu.
17/06/2020 14:06
Function
AND
0
0
0
0
0
0
0
0
The screen is organised into 3 areas:
1 - Section for setting the number of input groups operating in OR logic.
2 - Section for setting the number of input groups operating in AND logic.
3 - Setting the type of logic interaction between sections 1 and 2. AND or OR logic function.
The logic is set by pressing the button in the top right-hand corner. Each time the button is pressed, the logic function
changes. The selected logic is shown on the screen with a diagram representing the interaction between the input
group numbers for sections 1 and 2.
To enter an input group number, press the button and enter the number using the keypad.
CAUTION: it is important to know the input group numbers to be added to the logic diagram for the output
to be programmed in advance. We recommend creating a list that describes the correspondence between
the logic procedure for the input and for the output.
Example illustrating an output logic diagram setup:
17/06/2020 14:06
SAVE
Output Number
Name
Unlatched
Behaviour
NORMAL
Output polarity
0
Delay
CONTINUOUS
Output pulse type
Loop
Type
1
More
Edit Outputs Map
17/06/2020 14:06
Function
OR
1
0
0
0
2
0
0
0
Select a free output - in the example, this is number 1. Next, select the Output type - in the example, the type is an output loop
device. Press “Edit Outputs Map” to enter the logic map.
Enter the number of input groups, vertically (OR section) and horizontally (AND section).
The set parameters are shown with “an open switch” which represents an added logic procedure. Select the operating logic for
both sections.
In the example, output number 1 is enabled when one of the input groups 1 or 2 is active - OR logic.
If the operating logic is set to AND, output number 1 will only be enabled if both input groups 1 and 2 are active.
To save any new parameters, press “Save” on the main output screen.
1
2
3
17/06/2020 14:06
Function
OR
0
0
0
0
0
0
0
0